Enviro Test Transport Grounding Fault Transmission Line Tester

This Grounding Fault Transmission Line Tester has an operating temperature of 41° F to 104° F, test accuracy of 0.1 mA, and low power alarm of 24.5 V.

SKU: ETTTLT-149 Category:

Technical Specification

Output AC Detection Current 0 mA to 40±2 mA
Output AC Detection Voltage 0 kV to 3 kV
Output DC Grounding Impedance Current 0 mA to 36±2 mA
Output DC Grounding Impedance Voltage 0 V to 2.7 kV
Accuracy of Grounding Impedance Current ±1.0 mA
Output Accuracy of AC Detection Signal ±1.0 mA
Detect Line Length ≤62.31 mi (≤100 km)
Grounding Impedance Measurement 0 kΩ to 120 kΩ
Measurement Accuracy of Grounding Impedance Reading 5% ± 2 kΩ
Open Circuit Protection Time of Signal Circuit ≤2 S
Protection Time of Signal Output Circuit Integrity Detection ≤2 S
Detection Signal Fluctuation Alarm Threshold ±2 mA
Open Circuit Identification Current Threshold ≤2 mA
Low Power Alarm 24.5 V
Undervoltage Power-off 23 V
No Operation Automatic Power-off Time 0.5 Min to 10 Min
Rated Operating Voltage 25.9 V DC
Operating Voltage Range 23 V to 29.4 V
Battery Capacity 29.4 V or 9 AH
LCD Size 2.44 in x 1.73 in (62 mm × 44 mm)
Measuring Range 0.1 mA to 1200 A(50 Hz)
Sampling Frequency 0.1 mA to 200 mA(22 Hz)
Resolving Power 2 times/second
Test Accuracy 0.1 mA
Operating Temperature 41° F to 104° F (5° C to 40° C)
Storage Temperature 14° F to 104° F (-10° C to 40° C)
Storage Humidity <80% Rh
Interference 14° F to 140° F (-10° C to 60° C)
Size 18.30 in x 13.58 in x 7.28 in (465 mm x 345 mm x 185 mm)
Weight 21.34 lb (9.65 kg)

Reviews

There are no reviews yet.

Be the first to review “Enviro Test Transport Grounding Fault Transmission Line Tester”

Your email address will not be published. Required fields are marked *